THERMOCOUPLE TYPES
|
CODE |
CONDUCTOR COMBINATIONS |
NATIONAL STANDARDS
FOR OUTPUT OF THERMOCOUPLE CONDUCTORS |
Approximate Working Temperature Range of Measuring Junction. NB. Not Related to wire diameters and conductor insulating material. |
||
| +LEG | -LEG | Continuous | Short Term | ||
|
K |
NICKEL-CHROMIUM |
NICKEL-ALUMINIUM |
BS EN 60584,
1 Pt4:1996 |
0 to +1100 |
-180 to +1350 |
|
T |
COPPER |
COPPER-NICKEL |
BS EN 60584, 1 Pt3:1996 |
-185 to +300 |
-250 to +400 |
|
J |
IRON |
COPPER-NICKEL |
BS EN 60584, 1 Pt3:1996 |
+20 to +700 |
-180 to +750 |
|
N |
NICKEL-CHROMIUM- |
NICKEL-SILICON- |
BS EN 60584, 1 Pt8:1996 |
0 to +800 |
-40 to +900 |
|
E |
NICKEL-CHROMIUM |
COPPER-NICKEL |
BS EN 60584, 1 Pt6:1996 |
0 to +1100 |
-270 to +1300 |
|
R |
PLATINUM |
PLATINUM |
BS EN 60584, 1 Pt2:1996 |
0 to +1600 |
-50 to +1750 |
|
S |
PLATINUM |
PLATINUM |
BS EN 60584, 1 Pt1:1996 |
0 to 1550 |
-50 to +1750 |
|
B |
PLATINUM |
PLATINUM |
BS EN 60584, 1 Pt7:1996 |
+100 to +1600 |
+100 to +1820 |
|
G* |
TUNGSTEN |
TUNGSTEN |
There are no officially
recognized |
+20 to +2320 |
0 to +2600 |
|
C* |
TUNGSTEN |
TUNGSTEN |
There are no officially
recognized |
+50 to +1820 |
+20 to +2300 |
|
D* |
TUNGSTEN |
TUNGSTEN |
There are no officially
recognized |
0 to +2100 |
0 to +2600 |
| Home Page | Site Map | Section 1 | Section 2 | Section 3 | Section 4 |